PRODUCTS
Products
   
Feature
· Full Protection.
· DC Start Capability.
· Double Conversion UPS.
· External Battery Bank Available.
· Input and Output Neutral with Transformer Isolated.

Model
LUV-40
LUV-50
LUV-60
LUV-80
LUV-100
LUV-150
LUV-200
Capacity
4KVA
5KVA
6KVA
8KVA
10KVA
15KVA
20KVA
Input
Voltage
90 ~ 149VAC (115VAC) / 180 ~ 280VAC (230VAC)
Frequency
50Hz or 60Hz ± 5%
Phase
1P2W+G / 3P3W+G / 3P4W+G
Power Factor
0.8
Output
Voltage
115VAC or 230VAC ± 2%
Phase
1P2W+G
Voltage Regulation
± 1% at linear load
Frequency
50Hz or 60Hz ± 0.5%
Waveform Distortion
Pure Sine Wave less than 3% at full load
Crest Factor
3:1
Overload Capacity
100% ~ 124% continuous, >125% for 25 seconds, >135% to bypass
Efficiency AC to AC
>80% at battery fully charge
Battery
Type
Rechargeable, sealed maintenance free
Backup Time
10 minutes at full load and 25 minutes at half load
Recharge Time
4 ~ 8 hours 90% after fully discharge
Transfer Time
MainInverter
No break
Indicator
LCD Display
Input/Output & Battery Voltage, Frequency, Output Load, Operation Temperature
LED Display
Mimic display
Audible Alarm
Mains Fail
Sounds every 4 seconds after line fails
Battery Low
Sounds every second when approaches battery low level
UPS Fault
Continuous alarm
Protection
Short Circuit
When a short circuit occurs, the UPS will not transfer to Bypass but emit a sustained tone. Once the short circuit is removed, the tone stops and the whole system operates normally again. The UPS stops supplying power if the period of a short circuit is longer 3 seconds.
Lightning : Yes    Surge : Yes
Environment
Temperature
0C ~ 40C
Humidity
0% ~ 90%, non-condensing
Noise Level
<50dB at 1 meter
Communication
Interface Port
RS-232 or DB9
Dimension
W*H*D(mm)
UPS
260*800*660
260
900
660
310
900
660
360*740*870
Battery Bank
N/A
360*740*870
Net Weight
UPS
120kgs
130kgs
160kgs
190kgs
320kgs
190kgs
230kgs
Battery bank
N/A
200kgs
200kgs

Copyright © 1988- 2011 LONGTIME ELECTRONIC CO.,LTD. All rights reserved.