Model
|
LTH-10
|
LTH-20
|
LTH-30
|
LTH-40
|
LTH-50
|
LTH-60
|
LTH-80
|
LTH-100
|
|
|
Capacity
|
10KVA
|
20KVA
|
30KVA
|
40KVA
|
50KVA
|
60KVA
|
80KVA
|
100KVA
|
|
|
Input
(Rectifier)
|
Voltage
|
380VAC / 400VAC / 415VAC, 3 Phase 4 Wire
|
|||||||
|
Frequency
|
50Hz or 60Hz ± 5%
|
||||||||
|
Power Walk-in
|
0 ~ 100% : 10 seconds
|
||||||||
|
Output
(Inverter)
|
Voltage
|
380VAC / 400VAC / 415VAC, 3 Phase 4 Wire
|
|||||||
|
Frequency
|
50Hz or 60Hz ± 0.5%
|
||||||||
|
Static Regulation
|
± 1% at linear load
|
||||||||
|
Dynamic Regulation
|
<=2% at 50% load unbalance, <=5% at 100% load unbalance
|
||||||||
|
THD Distortion
|
<=3% at linear load, <=5% at non-linear load
|
||||||||
|
Transient Response
|
<5ms
|
||||||||
|
Power Factor
|
0.8
|
||||||||
|
Overload Capacity
|
100% ~ 124% for 10 minutes, >125% for 1 minute, >150% to bypass
|
||||||||
|
Battery
|
Voltage
|
192V (12V*16pcs)
|
348V (12V*29pcs)
|
||||||
|
Max. Charge Current
|
5A
|
10A
|
|||||||
|
Float Voltage
|
216V
|
392V
|
|||||||
|
Boost Voltage
|
230V
|
420V
|
|||||||
|
Recharge Time
|
4 ~ 8 hours 90% after fully discharge
|
||||||||
|
Static Switch
|
Main <-> Inverter
|
No break
|
|||||||
|
Indicator
|
LCD Display
|
Input / Output Voltage, Frequency, Output Loading Status, Battery Status, Battery Replacement Warning, Phase Site Wiring Error, Event Log
|
|||||||
|
LED Display
|
Mimic display
|
||||||||
|
Protection
|
Output Short
|
Yes
|
|||||||
|
Lighting/EMI Filter
|
Yes
|
||||||||
|
Environment
|
Temperature
|
0゚C ~ 40゚C
|
|||||||
|
Humidity
|
0% ~ 90%, non-condensing
|
||||||||
|
Noise Level
|
<60dB at 1 meter
|
<65dB at 1 meter
|
|||||||
|
Communication
|
Interface Port
|
RS-232 or DB9, SNMP adaptor (option), RS-485 (option), AS-400(option)
|
|||||||
|
Dimension
W*H*D(mm)
|
UPS
|
660*1550*800
|
660*1550*800
|
1110*1710*850
|
|||||
|
Battery Bank
|
660*1550*800
|
660*1550*800
|
|||||||
|
Net Weight
|
UPS
|
500kgs
|
600kgs
|
650kgs
|
700kgs
|
600kgs
|
700kgs
|
900kgs
|
1100kgs
|
|
Battery bank
|
430kgs
|
500kgs
|
630kgs
|
1100kgs
|
|||||