Model |
LVP-1000 |
LVP-1500 |
LVP-2000 |
LVP-3000 |
|
|
Capacity |
1000VA/800W |
1500VA/1200W |
2000VA/1600W |
3000VA/2400W |
|
|
Input |
Low Line Transfer |
160VAC/140VAC/120VAC/110VAC ± 5% or 80VAC/70VAC/60VAC/50VAC ± 5% (based on load percentage 100%~80% / 80%~70% / 70%~60% / 60%~0%) |
|||
|
Low Line Comeback |
175VAC ± 5% or 85VAC ± 5% |
||||
|
High Line Transfer |
300VAC ± 5% or 150VAC ± 5% |
||||
|
High Line Comeback |
290VAC ± 5% or 145VAC ± 5% |
||||
|
|
40Hz ~ 70Hz |
||||
|
Phase |
Single Phase with Ground |
||||
|
Power Factor |
>= 0.99 @ 220VAC ~ 230VAC (input voltage) |
||||
|
Output |
Output Voltage |
200 / 208 / 220 / 230 / 240VAC or 100 / 110 / 115 / 120 / 127VAC |
|||
|
AC Voltage Regulation |
± 3% (batt. mode) |
||||
|
(synchronized range) |
47Hz ~ 53Hz or 57Hz ~ 63Hz |
||||
|
(batt. mode) |
50Hz ± 0.25Hz or 60Hz ± 0.3Hz |
||||
|
Overload |
100% ~ 110% : Audible warning 110% ~ 130% : UPS shuts down in 30 seconds at battery mode or transfers to bypass mode when the utility is normal > 130% : UPS shuts down immediately at battery mode or transfers to bypass mode when the utility is normal |
||||
|
Current Crest Ration |
3 : 1 |
||||
|
Harmonic Distortion |
<= 3% THD (linear load) <= 6% THD (non-linear load) |
<= 4% THD (linear load) <= 7% THD (non-linear load) |
|||
|
Transfer Time |
AC Mode to Batt. Mode : 0 |
||||
|
Inverter to Bypass : 4ms (typical) |
|||||
|
Waveform (batt. mode) |
Pure Sine Wave |
||||
|
Efficiency |
AC Mode |
~ 85% |
~ 88% |
||
|
|
~ 83% |
||||
|
Alarm |
|
Sounding every 4 seconds |
|||
|
Low |
Sounding every second |
||||
|
Overload |
Sounding twice every second |
||||
|
Fault |
Continuously sounding |
||||
|
Indicator |
LCD Display |
UPS status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault |
|||
|
(Standard Model) |
|
12V / 7AH |
12V / 9AH |
12V / 7AH |
12V / 9AH |
|
Numbers |
3 |
3 |
6 |
6 |
|
|
Recharge Time |
4 hours recover to 90% capacity (typical) |
||||
|
Charging Current |
|
||||
|
Charging Voltage |
41.0VDC ± 1% |
82.1VDC ± 1% |
|||
|
(Long-run Model) |
|
Depending on the capacity of external batteries |
|||
|
Charging Current |
|
||||
|
Charging Voltage |
41.0VDC ± 1% |
82.1VDC ± 1% |
|||
|
Communication |
RS-232 or USB |
Support WIN 2000/2003/XP/2008/7 , Linux , MAC |
|||
|
SNMP (optional) |
Power management from SNMP manager and web browser |
||||
|
Environment |
Humidity |
20 ~ 90% RH @ 0~40゚C (non-condensing) |
|||
|
Noise |
Less than 45dB at |
||||
|
Dimension |
Tower Case (DxWxH) |
397 x 145 x |
421 x 190 x |
||
|
Rack Case (DxWxH) |
420 x 438 x |
580 x 438 x |
|||
|
Net Weight |
Tower Case |
13kgs |
14kgs |
26kgs |
28kgs |
|
Rack Case |
16kgs |
17kgs |
29kgs |
31kgs |
|